Modbus polling cycle calculator
Quick answer: a Modbus RTU scan cycle is set by frame time, not by the PLC. At 9,600 baud, one 25-register read costs roughly 90–120 ms once slave latency and the inter-frame gap are counted — so ten devices land near a one-second cycle no matter how fast the master polls. Put your numbers in; the frame math is below the result.
Inputs
Result
| Requests per device | – |
|---|---|
| Time per request | – |
| Cycle per device | – |
| Full scan cycle (all devices) | – |
| Achievable scan rate | – |
How it is calculated
Each request/response pair costs: request frame (8 bytes) + response frame (5 + 2 × registers in that request bytes), sent at 11 bits per byte (1 start, 8 data, parity, 1 stop). Add the slave latency and the Modbus inter-frame gap of 3.5 character times (1.75 ms fixed above 19,200 baud). Retries, exception responses and write traffic are not counted — treat the result as the best case a healthy bus can reach.
Related: Polling vs publish for legacy machine data · Gateway records with Modbus RTU ports